FULL LOAD CURRENT IN AMPERES, THREE PHASE CIRCUITS*

3 PHASE KVA= VOLTS x AMPSx1.73
1000

KVA 208V 240V 480V
3 8.3 7.2 3.6
4 12.5 10.8 5.4
6 16.6 14.4 7.2
9 25.0 21.6 10.8
15 41.0 36.0 18.0
22 62.0 54.0 27.0
30 83.0 72.0 36.0
45 124.0 108.0 54.0
75 208.0 180.0 90.0
112 312.0 270.0 135.0
150 416.0 360.0 189.0
225 624.0 541.0 270.0
300 832.0 721.0 360.0

*When motor service factor is greater than 1, increase full load amps proportionally. Example: If service factor is 1.15, increase above amp values by 15%.

   